RGS FIRE-PROOF SCROLLING SHUTTER

Trouble-free service and convenience

Fire-proof scrolling shutters are custom-made according to the customer’s dimensional requirements. They are tested
according to European standards (ČSN EN) and can be supplied in various versions.

Thanks to its simple structural design, the installation takes up a minimal amount of space. The horizontal lamellas,
manufactured from high-quality galvanized zinc-plated sheet profiles, are joined together by a locking joint. The lateral
guide rails ensure smooth vertical movement of the scrolling shutter. The doorjamb and header are lined with an insulation
profile produced from an intumescent material.

RGS Fire Proof Roller Shutter download data sheet

TYPES OF SCROLLING SHUTTERS
foto1 foto2

Insulated RGS-60 - EI 60 to 120 DP1-C3, EW 180 DP1-C3

  • insulated lamellas each 150 mm tall and 60 mm thick
    with a perfectly interrupted thermal bridge
  • insulation density of 30 kg/m3 for the EI 60 class door
  • insulation density of 35 kg/m3 for the EI 120 class door
  • considering the large diameter of the rolled-up shutter, the motor
    is always placed outside the drum and power is transferred through
    cog wheels placed on the shafts of the drum and motor
  • individual lamellas can be fitted during the installation
  • can also be used for sound insulation
  • diameter of rolled-up shutter: 670–950 mm
  • certified without requiring a cover for the rolled-up shutter
foto3 foto4

Non-insulated RGS-NI-NI - EW  30 DP1-C3

  • non-insulated thin-walled sheet lamellas each 100 mm tall
  • the motor shaft can be attached directly to the shaft of the main
    drum (does not apply for FS motors)
  • drum and shutter can only be installed as a single unit
  • diameter of rolled-up shutter:310 – 500 mm
  • certified without requiring a cover for the rolled-up shutter
foto5

Insulated RGS-H - EI 60 to 120 DP1-C3, EW 180 DP1-C3

  • combination of insulated and non-insulated lamellas that slide
    horizontally with a perfectly interrupted thermal bridge
    for the insulated lamellas
  • the non-insulated lamellas, which are scrolled onto the drum, drag
    the insulated lamellas along a horizontal steel structure (similar
    to sectional doors)
  • benefit of maintaining a low head (450 mm) and high fire
    resistance for doors
  • the motor shaft can be attached directly to the shaft of the main
    drum (does not apply for FS motors)
  • can also be used for soundinsulation
  • diameter of rolled-up shutter: 310 – 500 mm
SURFACE FINISHING 
foto6

Zinc-plated

  • plating with high-quality galvanized zinc-plated sheets, which need no further surface
    treatment
foto7  

Color coating

  • RAL according to the purchaser’s selection – Individual lamellas are delivered already
    painted
  • considering the nature of scrolling shutters, which cause the lamellas to rub against one
    another, no guarantee against damage to the coating can be provided
GATE CONTROL
foto8

FS (fail-safe) motor with FSTronic control

  • industrial motor with long cycle life up to 100,000 cycles
  • 3x400 V/10 A supply
  • under normal operation, the motor opens and closes the gate
  • in case of an alarm, the gate closes by gravity (fail-safe)
  • the gate cannot be opened mechanically
  • power must be transferred from the motor to the drum by a drive chain
foto9

 

FDF motor with FSTronic 24 control

  • industrial motor with long cycle life up to 100,000 cycles
  • 3x400 V/10 A supply
  • under normal operation, the motor opens and closes the gate
  • in case of an alarm, the gate is closed by means of a 24 V DC battery powered reserve motor
  • the gate can be opened mechanically
 foto10   

SI (KE) motor with 6RM4 control

  • industrial motor with long cycle life up to 100,000 cycles
  • SI motor is intended for RGS-NI and is placed directly onto the shaft
  • KE motor is intended for RGS-60 and power is transferred to the drum by a drive chain
  • 1x230 V/20 A supply
  • under normal operation, the motor opens and closes the gate
  • smooth operation thanks to the frequency inverter increases the life of the gate
  • speed can be easily regulated on the frequency inverter
  • in case of an alarm, the motor closes the gate by means of the UPS emergency power supply
  • the gate can be opened mechanically
  • optionally, the gate can be opened electronically from the UPS emergency power supply

If this option is required, it is necessary to contact the manufacturer to determine the size of the
UPS (standard UPS sized only for closing).

 foto11
 foto12

 

Tubular motor with Rolltronic control

  • tubular motor is not appropriate for a constant load
  • only for control in “dead man” mode
  • only for RGS-NI up to 7 m2
ELECTRONIC ACCESSORIES
 příslušenství Flashni

Siren with warning light

  • FLASHNI low-consumption light and sound signalization of door motion
 
 příslušenství detekce  

Autonomous detection system

  • control device for closing doors in locations not equipped with EFS
  • two detectors are supplied as standard, with one installed on either side of the door
  • detectors are supplied in these variants: smoke, temperature and combined
 pohybove cidlo  

Motion detector

  • infrared motion sensor responding to movement in front of the door
  • after the door opens, it then automatically closes after a set time
  příslušenství dálkový ovladač  

Remote control

  • single- or multi-channel mobile remote control device in industrial configuration allowing remote door opening
  • a receiver, which is not a standard part of the control unit, must be installed in order to use the remote
    control
 příslušenství tahový spínač  

Pull switch

  • a pull switch ensures automatic opening for transit of materials handling machinery
 příslušenství světelná clona

Photodetector

  • safety optical sensing strip emits multiple beams for motion detection
  • prevents collision of closing doors with a passing person or object
 RGS spodni bezpecnostni lista

Bottom safety strip

  • safety strip using the system of OSE or 8K2 optical strips placed in the aluminum profile
  • must be installed along with a control unit for the bottom safety strip
MECHANICAL ACCESSORIES
foto13

Roll-up cover

  • compact cover of the rolling track with individual parts from zinc-plated sheets
  • installation is not necessary for fire resistance; the door is tested and certified even without
    the cover

foto14

foto15foto16